Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2017, 07:01 AM
  • 01 0541A_01 0541_29062017_012048.mp4

Date
06/28/2017
W/O
640684
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00206
PipeID
P01030
Time
12:01 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3976-SC342139
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_640684_TV01243_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0541A
Downstream MH
01 0541
Dir. of Survey
Downstream
Length Surveyed
328 ft.
Total Length
328 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
3
Overall Quick
Overall Rating
323
Pipe schematic from manhole 01 0541A to 01 0541
MH: 01 0541AMH: 01 0541downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0541A6.1 ft. SAV - Surface Aggregate Visible, from 12 to 12 o'clock, within 8 inches of joint: YES, Start6.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"49.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"69.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"99.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"112.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"164.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"166.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"210.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"225.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"255.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"272.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"299.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"301.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES325.4 ft. SAV - Surface Aggregate Visible, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish325.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328 ft. AMH - Downstream Manhole, Survey Ends - 01 0541

Observation photos (3)

  • Surface Aggregate Visible, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Surface Aggregate Visible, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    301.1 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
299.9TF
8.3TF
272.5TF
99.9TF
325.4SAV
325.4DAGS
328AMH01 0541
49.1TF
6.1SAV
0MWL
225.1TF
164.2TF
255.2TF
0MWM
6.1DAGS
0AMH01 0541A
166.8TF
210.1TF
112.6TF
69.4TF
301.1FL

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-06-28T00:01:19-07:00