Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2016, 07:45 AM
  • B 1205_B 1204_060316_004532.mp4

Date
06/03/2016
W/O
574364
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13525
Time
12:45 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3389
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
WO_574364_TV16042_JUNE2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1205
Downstream MH
B 1204
Dir. of Survey
Downstream
Length Surveyed
102.9 ft.
Total Length
102.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole B 1205 to B 1204
MH: B 1205MH: B 1204downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 12050 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.2 ft. MGO - General Observation - MAG COAT 90%102.9 ft. AMH - Downstream Manhole, Survey Ends - B 1204

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0AMHB 1205
0MWL
2.2SAV
102.9AMHB 1204
0MWM
2.2MGOMAG COAT 90%

Properties (3)

custom_field_two
5
customer
LACSD
datetime