Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2017, 07:07 AM
  • 16 0557_16 0556 _28092017_000823.mp4

Date
09/28/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13608
Time
12:07 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4279
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Square
Height
24 in.
Width
24 in.
Upstream MH
16 0557
Downstream MH
16 0556
Dir. of Survey
Downstream
Length Surveyed
313.5 ft.
Total Length
313.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
2K11
O&M Rating
125
Overall Index
2
Overall Quick
Overall Rating
308
Pipe schematic from manhole 16 0557 to 16 0556
MH: 16 0557MH: 16 0556downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05570 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2.9 ft. MGO - General Observation - MAG COAT START3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start8.6 ft. RFJ - Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES19.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"120.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"124.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"155.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4"173.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"225.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"271 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"278.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"310.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish310.3 ft. MGO - General Observation - MAG COAT FINISH310.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish313.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0556

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES

    8.6 ft. - Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
310.3SAV
278.3TFC
120.9TFA
8.6RFJ
19.1TFA
3SAV
155.8TB
0AMH16 0557
310.3MGOMAG COAT FINISH
225.7TBA
0MWL
310.3DAGS
0MWM
173.4TFA
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
271TBA
2.9MGOMAG COAT START
124.6TBA
2.7DAGS
313.5AMH16 0556

Properties (5)

additional_info
SC352124
custom_field_two
3
customer
LACSD
datetime
2017-09-28T00:07:43-07:00
year_laid
37734