Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2017, 10:59 AM
  • 05 0717_05 0716_25092017_035937.mpg

Date
09/25/2017
W/O
658045
Weather
Dry
Operator/Surveyor
CORTEZ ESTEBAN
Sewer ID
Z00521
PipeID
P05940
Time
3:59 AM
Certificate
U-209-8148
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
K4939
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0717
Downstream MH
05 0716
Dir. of Survey
Downstream
Length Surveyed
314.8 ft.
Total Length
314.8 ft.
Structural Index
2
Structural Quick
322A
Structural Rating
30
O&M Index
2
O&M Quick
4132
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
43
Pipe schematic from manhole 05 0717 to 05 0716
MH: 05 0717MH: 05 0716downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07170 ft. MWL - Water Level, 10 %of cross sectional area2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start29.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish29.3 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR32.3 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start50.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start50.1 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Finish116.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES120 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES122.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES138 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES143.8 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES173.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 4"173.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish173.8 ft. RBJ - Roots Ball Joint, from 08 to 04 o'clock, 65 %, within 8 inches of joint: YESR - LINE HAS BEEN CLEANED176.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start251.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish270 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES270 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES288.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES291.1 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES297.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES300.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES303.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES303.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES309.1 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES314.8 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH314.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0716

Observation photos (21)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR

    29.3 ft. - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start

    32.3 ft. - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    50.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    116.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    120 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    122.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    138 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    143.8 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish

    173.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish

  • Roots Ball Joint, from 08 to 04 o'clock, 65 %, within 8 inches of joint: YESR - LINE HAS BEEN CLEANED

    173.8 ft. - Roots Ball Joint, from 08 to 04 o'clock, 65 %, within 8 inches of joint: YESR - LINE HAS BEEN CLEANED

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    176.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    270 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    270 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    288.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    291.1 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    297.3 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    300.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    303.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    303.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

    309.1 ft. - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (30)

DistanceCodeObservation
300.1CL
270CL
303.1CL
2RFJ
314.8MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
116.8CL
143.8CL
32.3RMJ
173.4TB
297.3CL
50.1RFJ
0MWM
309.1CM
270CL
291.1CL
0AMH05 0717
314.8AMH05 0716
0MWL
251.3RFJ
173.8RFJ
173.8RBJLINE HAS BEEN CLEANED
29.2RFJ
122.9CL
288.3CL
303.1CL
176.6RFJ
120CM
50.1RMJ
29.3RMJ
138CL

Properties (4)

additional_info
SC345847
custom_field_two
3
customer
LACSD
datetime
2017-09-25T03:59:06-07:00