Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2017, 08:25 AM
  • 08 0178_08 0177_29092017_012536.mp4

Date
09/29/2017
W/O
657890
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00236
Time
1:25 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4893
Sewer Name
08 GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0177
Downstream MH
08 0178
Dir. of Survey
Upstream
Length Surveyed
334.4 ft.
Total Length
334.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 08 0177 to 08 0178
MH: 08 0177MH: 08 0178upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 01780 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK1.4 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH7.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES60.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"63.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"110.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"113.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"160.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"163.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"213.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6"213.8 ft. RML - Roots Medium Lateral, at 02 o'clock, 30 %, within 8 inches of joint: YES215.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"263 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: YES, 6"266.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"313.1 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES313.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"316.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"334.4 ft. MWM - Water Mark, 15 %of cross sectional area334.4 ft. MWL - Water Level, 10 %of cross sectional area334.4 ft. AMH - Downstream Manhole, Survey Begins - 08 0177

Observation photos (1)

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES

    21.3 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
0MWM
333MGOSPALLING THROUGHOUT THE REACH
174.2TFC
326.6DAGS
171.3TFC
71.4TFB
21.3RFJ
21.2TF
271.1TFC
334.4AMH08 0178
273.5TFC
0MWL
120.6TF
220.8TFC
0AMH08 0177
334.4MGOCONNECTION AT MH 3 O'CLOCK
17.6TFC
120.6RML
68.2TFC
223.8TF
118.8TFC

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-09-29T01:25:16-07:00