Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 2, 2017, 10:15 AM
  • J 0006_J 0005 _20170802_051106.mp4

Date
08/02/2017
W/O
646290
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00060
PipeID
P11594
Time
3:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4675
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_646290_TV08100_JUL2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0006
Downstream MH
J 0005
Dir. of Survey
Downstream
Length Surveyed
643.5 ft.
Total Length
643.5 ft.
Structural Index
3
Structural Quick
3X2X
Structural Rating
624
O&M Index
2
O&M Quick
412X
O&M Rating
256
Overall Index
2
Overall Quick
Overall Rating
880
Pipe schematic from manhole J 0006 to J 0005
MH: J 0006MH: J 0005downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00060 ft. MWM - Water Mark, 55 %of cross sectional area13.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start13.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start26 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start643.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish643.5 ft. MGO - General Observation - CONNECTION AT 3 OC643.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish643.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish643.5 ft. AMH - Downstream Manhole, Survey Ends - J 0005643.5 ft. MGO - General Observation - CONNECTION AT 9 OC

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    13.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    13.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    26 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
643.5SAV
13.7DAGS
643.5MGOCONNECTION AT 3 OC
0MWL
643.5SSS
643.5DAGS
0AMHJ 0006
643.5AMHJ 0005
26SAV
0MWM
643.5MGOCONNECTION AT 9 OC
13.7SSS

Properties (4)

additional_info
SC345613
custom_field_two
3
customer
LACSD
datetime
2017-08-02T03:15:34-07:00