Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2017, 02:40 PM
Date
11/04/2017
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01462
Time
7:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6860
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine assessment
Project
JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
G 0139
Downstream MH
G 0138
Dir. of Survey
Downstream
Length Surveyed
332.6 ft.
Total Length
332.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
203
Pipe schematic from manhole G 0139 to G 0138
MH: G 0139MH: G 0138downstream0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. MGO - General Observation - MH CONN 3:00 STUB0 ft. MGO - General Observation - MH CONN 9:00 STUB0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 7:40AM2 ft. MGO - General Observation - MAG COAT 75% 10:00 TO 2:00 START2 ft. MGO - General Observation - MISSING TILES 30% POSSIBLE UNDER MAG START 9:00 TO 3:002 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES198.8 ft. MGO - General Observation - POSSIBLE MISSING TILES UNDER MAG COAT245.3 ft. MGO - General Observation - 70% MAG COAT332.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES332.2 ft. MGO - General Observation - MH CONN 3:00 STUB332.2 ft. MGO - General Observation - MH CONN 9:00 ACTIVE332.2 ft. MGO - General Observation - 70% MAG COAT FINISH332.2 ft. MGO - General Observation - 30% MISSING TILES POSSIBLE UNDER MAG COAT332.6 ft. AMH - Downstream Manhole, Survey Ends - 8:05AM

Observation photos (4)

  • General Observation - MAG COAT 75% 10:00 TO 2:00 START

    2 ft. - General Observation - MAG COAT 75% 10:00 TO 2:00 START

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - POSSIBLE MISSING TILES UNDER MAG COAT

    198.8 ft. - General Observation - POSSIBLE MISSING TILES UNDER MAG COAT

  • General Observation - 70% MAG COAT

    245.3 ft. - General Observation - 70% MAG COAT

Observations (16)

DistanceCodeObservation
0MWL
0MGOMH CONN 3:00 STUB
245.3MGO70% MAG COAT
332.2SAVSEVERE AGG AREAS OF MISSING TILES
2MGOMAG COAT 75% 10:00 TO 2:00 START
2MGOMISSING TILES 30% POSSIBLE UNDER MAG START 9:00 TO 3:00
332.2MGOMH CONN 3:00 STUB
332.2MGOMH CONN 9:00 ACTIVE
332.6AMH8:05AM
0MGOMH CONN 9:00 STUB
198.8MGOPOSSIBLE MISSING TILES UNDER MAG COAT
332.2MGO70% MAG COAT FINISH
2SAVSEVERE AGG AREAS OF MISSING TILES
332.2MGO30% MISSING TILES POSSIBLE UNDER MAG COAT
0MWM
0AMH7:40AM

Properties (4)

custom_field_three
MISSING TILES - SEVERE AGG VISIBLE
custom_field_two
4
customer
LACSD
datetime
2017-11-04T07:40:03-07:00