Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2018, 10:23 AM
  • 29 0268A_29 0268 _05102018_015044.mpg

Date
10/05/2018
W/O
729275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24174
Time
3:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6131
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_729275_TV29063_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0268
Downstream MH
29 0268A
Dir. of Survey
Upstream
Length Surveyed
225 ft.
Total Length
225 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 29 0268 to 29 0268A
MH: 29 0268MH: 29 0268Aupstream0 ft. ACOM - Cleanout Mainline, Survey Ends - 29 0268A4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"11 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"44 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"157 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"219 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start221 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES225 ft. MWL - Water Level, 5 %of cross sectional area225 ft. MWM - Water Mark, 5 %of cross sectional area225 ft. AMH - Downstream Manhole, Survey Begins - 29 0268

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
214CM
0MWL
4FM
221TFC
139TFC
68TF
158TF
6CM
214TF
121TFC
0MWM
181TF
172TFC
0AMH29 0268
225ACOM29 0268A
77TFC
79TFC

Properties (4)

additional_info
SC364850
custom_field_two
3
customer
LACSD
datetime
2018-10-05T03:23:19-07:00