Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2018, 06:41 AM
  • 29 0689_29 0264 _04102018_234215.mpg

Date
10/04/2018
W/O
729275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24169
Time
11:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6131
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_729275_TV29063_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0689
Downstream MH
29 0264
Dir. of Survey
Downstream
Length Surveyed
348 ft.
Total Length
348 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 29 0689 to 29 0264
MH: 29 0689MH: 29 0264downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 068928 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"187 ft. FS - Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES191 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES193 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"196 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"254 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"297 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"307 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES316 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start330 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"348 ft. AMH - Downstream Manhole, Survey Ends - 29 0264

Observation photos (4)

  • Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

    187 ft. - Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    191 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    307 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    316 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
330CM
187FS
196TFC
316CM
297TFC
191FM
0MWM
193TF
73TF
0MWL
307CM
28TFC
254TFC
0AMH29 0689
330TF
348AMH29 0264

Properties (4)

additional_info
SC364850
custom_field_two
3
customer
LACSD
datetime
2018-10-04T23:41:00-07:00