Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2018, 07:25 AM
  • 05 1590_05 1589_1112018_012618.mp4

Date
11/01/2018
W/O
0736672
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00485
PipeID
P06814
Time
12:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1036
Sewer Name
05 MARICOPA STREET TRUNK
City
T0RRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
26
Purpose
Capital Improvement Program Assesment
Project
20181026MDM_MARICOPA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1589
Downstream MH
05 1590
Dir. of Survey
Upstream
Length Surveyed
336.8 ft.
Total Length
336.8 ft.
Structural Index
2
Structural Quick
3A2B
Structural Rating
60
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
65
Pipe schematic from manhole 05 1589 to 05 1590
MH: 05 1589MH: 05 1590upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:10AM0.8 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS0.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 30% HAIRLINE AT JOINTS0.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS0.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS114.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped129.2 ft. MGO - General Observation - LINK PIPE129.7 ft. MGO - General Observation - DAMAGED TABS LINK PIPE 8-12:00129.7 ft. MGO - General Observation - LINK PIPE130.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active152.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open165.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped-70% ROOTS165.2 ft. RML - Roots Medium Lateral, at 10 o'clock, 5 %, within 8 inches of joint: YES173.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AR JOINTS173.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS173.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS173.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS179.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H180.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open189.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H189.4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H204.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H210.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H219.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL234.3 ft. MGO - General Observation - 15" VCP240.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H240.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H245.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H260.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H267.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped270.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H270.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H293.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H293.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL303.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H309 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start309 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H315.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped319.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE319.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE324.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL328.8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT328.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT336.8 ft. MWL - Water Level, 10 %of cross sectional area336.8 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active336.8 ft. AMH - Downstream Manhole, Survey Begins - 1:30AM336.8 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    27.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 15" VCP

    102.5 ft. - General Observation - 15" VCP

  • General Observation - DAMAGED TABS LINK PIPE 8-12:00

    207.1 ft. - General Observation - DAMAGED TABS LINK PIPE 8-12:00

  • General Observation - LINK PIPE

    207.1 ft. - General Observation - LINK PIPE

  • General Observation - LINK PIPE

    207.6 ft. - General Observation - LINK PIPE

Observations (49)

DistanceCodeObservation
102.5MGO15" VCP
206.1TFActive
12.5FCSL
207.6MGOLINK PIPE
147.4FLH
147.4FCH
222.5TFCCapped
336MGOConn. @ Mh, 3 O' Clock. Active
336FC20% SLIGHT AT JOINTS
8FCSLIGHT
0MWL
90.9FLH
69.5TFCCapped
27.8DAGS
126.7FCH
184.4TFOpen
21.6TFCCapped
76.2FLH
207.1MGODAMAGED TABS LINK PIPE 8-12:00
8FCSLIGHT
207.1MGOLINK PIPE
163FCHAIRLINE AR JOINTS
33.1FCH
65.9FLH
96.4FCH
17.7FCHAIRLINE
132.2FCH
171.6TFCCapped-70% ROOTS
0MGOConn. @ Mh, 9 O' Clock. Active
0AMH1:30AM
336FC30% HAIRLINE AT JOINTS
163FCSLIGHT AT JOINTS
43.1FLH
96.4FLH
117.1FCSL
157.6FCH
163FLHAIRLINE AT JOINTS
163FLSLIGHT AT JOINTS
27.8FLH
336DAGS
0MWM
156.5TFOpen
17.7FCHAIRLINE
65.9FLH
336FL10% HAIRLINE AT JOINTS
171.6RML
336FL10% SLIGHT AT JOINTS
336.8AMH2:10AM
43.1FCSL

Properties (4)

custom_field_three
SLIGHT FRACTURES--LINK PIPE BENT TABS
custom_field_two
3
customer
LACSD
datetime
2018-11-01T00:25:30-07:00