Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 10:09 AM
  • 18 0669_18 0668 _21112017_020924.mpg

Date
11/21/2017
W/O
668744
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14518
Time
2:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5042
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA, CA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_668744_TV18081_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
347.6 ft.
Total Length
347.6 ft.
Structural Index
2
Structural Quick
3226
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06690 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area26.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start40.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"46.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish46.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start82.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish82.1 ft. CS - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES94.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.5 ft. CS - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES142.9 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start152.9 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish152.9 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES187.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start195.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.5 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES296.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"302.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"347.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish347.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0668

Observation photos (8)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    26.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    46.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    82.1 ft. - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

    122.5 ft. - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start

    142.9 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    152.9 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    187.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Broken, at 12 o'clock, within 8 inches of joint: YES

    208.5 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
208.5B
26.4CL
187.7CM
40.8TF
82.1CL
347.6CM
142.9CL
46.6CL
82.1CS
296.9TFC
0AMH18 0669
0MWL
200.9TFC
94.6TF
195.5TFC
46.7CL
347.6AMH18 0668
99.7TF
152.9CL
152.9CS
0MWM
302.1TFC
122.5CS

Properties (4)

additional_info
SC346271
custom_field_two
3
customer
LACSD
datetime
2017-11-21T02:09:07-08:00