Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2016, 05:58 AM
  • 02 1598_02 1597_20160816_001438.mpg

Date
08/15/2016
W/O
585987
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00231
PipeID
P04053
Time
10:58 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3420
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_585987_TV02010_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1598
Downstream MH
02 1597
Dir. of Survey
Downstream
Length Surveyed
328.9 ft.
Total Length
328.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2L11
O&M Rating
131
Overall Index
2
Overall Quick
Overall Rating
133
Pipe schematic from manhole 02 1598 to 02 1597
MH: 02 1598MH: 02 1597downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 15980 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start90.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"204.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"227.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES252.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"325.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.9 ft. VC - Vermin Cockroach328.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1597328.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK328.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    90.1 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    204.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    227.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    252.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • General Observation - CONNECTION AT THE MH 3 O'CLOCK

    328.9 ft. - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observations (15)

DistanceCodeObservation
328.9VC
252.1TFC
0MWM
328.9AMH02 1597
325.9DAGS
204.5TFC
0MWL
227.5CL
2DAGS
0AMH02 1598
0MGOCONNECTION AT THE MH 3 O'CLOCK
328.9MGOCONNECTION AT THE MH 3 O'CLOCK
0MGOCONNECTION AT THE MH 9 O'CLOCK
90.1TF
328.9MGOCONNECTION AT THE MH 9 O'CLOCK

Properties (4)

additional_info
SC305973
custom_field_two
4
customer
LACSD
datetime
2016-08-15T22:58:33-07:00