Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2016, 08:54 AM
  • B 1143_B 1142 _060216_015515.mp4

Date
06/02/2016
W/O
574365
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13445
Time
1:54 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3388
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_574365_TV16044_JUNE2016
Sewer Type
Gravity
Material
BRICK
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1143
Downstream MH
B 1142
Dir. of Survey
Downstream
Length Surveyed
722.6 ft.
Total Length
722.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1143 to B 1142
MH: B 1143MH: B 1142downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11430 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK53.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"92.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"94.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"301.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6"376.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"399.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"400.9 ft. MMS - Mortar Missing Small, at 03 o'clock416.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"470.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"505.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"571.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"623.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"673.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"710.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"722.6 ft. AMH - Downstream Manhole, Survey Ends - B 1142

Observation photos (1)

  • Mortar Missing Small, at 03 o'clock

    400.9 ft. - Mortar Missing Small, at 03 o'clock

Observations (23)

DistanceCodeObservation
400.9MMS
673.6TFC
399.3TF
144.9TFC
195.3TFC
0MWL
247.1TF
53.2TFC
301.8TFC
195.3TFC
470.1TF
722.6AMHB 1142
0MWM
710.2TF
416.8TFC
0AMHB 1143
92.6TB
94.2TFC
376.4TF
0MGOCONNECTION AT MH 9 OCLOCK
505.9TFC
623.9TFC
571.7TFC

Properties (4)

additional_info
SC300388
custom_field_two
4
customer
LACSD
datetime
2016-06-02T01:54:28-07:00