Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2016, 08:09 AM
Date
06/03/2016
W/O
574364
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13523
Time
1:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3389
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
WO_574364_TV16042_JUNE2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1203
Downstream MH
B 1202
Dir. of Survey
Downstream
Length Surveyed
147 ft.
Total Length
147 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
87
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
87
Pipe schematic from manhole B 1203 to B 1202
MH: B 1203MH: B 1202downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 12032 ft. SAV - Surface Aggregate Visible, at 04 o'clock, within 8 inches of joint: NO, Start - RIGHT BELOW THE MAG5.5 ft. MGO - General Observation - MAG COAT 90%43.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"145 ft. SAV - Surface Aggregate Visible, at 04 o'clock, within 8 inches of joint: NO, Finish147 ft. AMH - Downstream Manhole, Survey Ends - B 1202

Observations (9)

DistanceCodeObservation
145SAV
0MWL
2SAVRIGHT BELOW THE MAG
147AMHB 1202
0MWM
43.5TF
0AMHB 1203
122TF
5.5MGOMAG COAT 90%

Properties (4)

additional_info
SC300389
custom_field_two
3
customer
LACSD
datetime
2016-06-03T01:09:00-07:00