Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 16, 2016, 06:24 AM
  • 05 1658A_05 1658 _061516_232520.mpg

Date
06/15/2016
W/O
563399
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06881
Time
11:24 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3398
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
WO_563399_TV05132_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1658A
Downstream MH
05 1658
Dir. of Survey
Downstream
Length Surveyed
271.3 ft.
Total Length
271.3 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
158
Pipe schematic from manhole 05 1658A to 05 1658
MH: 05 1658AMH: 05 1658downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 1658A2.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"7.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start64.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO101.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"201.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"266.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish271.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK271.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK271.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1657A271.3 ft. MGO - General Observation - NO MH 05 1658 AT MH 05 1657A

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO

    64.5 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
0MWM
0MGOCONNECTION AT THE MH 3 O'CLOCK
0MWL
2.3TFC
64.5DSZ
271.3MGOCONNECTION AT THE MH 9 O'CLOCK
201.3TFC
101.4TFC
271.3MGOCONNECTION AT THE MH 3 O'CLOCK
271.3AMH05 1657A
0MGOCONNECTION AT THE MH 9 O'CLOCK
7.4CM
271.3MGONO MH 05 1658 AT MH 05 1657A
0AMH05 1658A
266.6CM

Properties (4)

additional_info
SC300398
custom_field_two
3
customer
LACSD
datetime
2016-06-15T23:24:45-07:00