Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2017, 09:02 AM
  • Section#3_F 0030_F 0029__852017__G6792.mp4

Date
08/05/2017
W/O
0646716
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10120
Time
2:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6792
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20170805MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0030
Downstream MH
F 0029
Dir. of Survey
Downstream
Length Surveyed
527.2 ft.
Total Length
527.2 ft.
Structural Index
4
Structural Quick
5M4T
Structural Rating
760
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
764
Pipe schematic from manhole F 0030 to F 0029
MH: F 0030MH: F 0029downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:002.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR18.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT90 ft. SRC - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN109.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE329.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR UNDER MAG COAT511.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR526.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVEREV AGG526.6 ft. MGO - General Observation - MAG COAT 80% FINISH527.2 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observation photos (6)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    18.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN

    90 ft. - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    511.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (14)

DistanceCodeObservation
526.6SAMSEVEREV AGG
2.3SRVCIRCUM REBAR
526.6MGOMAG COAT 80% FINISH
18.3SRVCIRCUM REBAR UNDER MAG COAT
2SAMSEVERE AGG
0MWL
109.9TFACTIVE
2MGOMAG COAT 80% START 9:00 TO 3:00
329.2SRVCIRCUM REBAR UNDER MAG COAT
0MWM
527.2AMH4:00AM
90SRCCIRCUM REBAR BROKEN
511.9SRVCIRCUM REBAR
0AMH3:30AM

Properties (4)

custom_field_three
CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2017-08-05T02:02:13-07:00