Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2017, 03:39 PM
  • 19 0091_19 0090_842017_103122.mp4

Date
08/04/2017
W/O
0640724
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00722
PipeID
P15283
Time
8:39 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7481
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
LAKEWOOD
Loc. details
Yard
Location Code
Y
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170804SHO_EAST_ARTESIA_TRUNK_SECTS_1235
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0090
Downstream MH
19 0091
Dir. of Survey
Upstream
Length Surveyed
168.9 ft.
Total Length
168.9 ft.
Structural Index
5
Structural Quick
5931
Structural Rating
48
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
52
Pipe schematic from manhole 19 0090 to 19 0091
MH: 19 0090MH: 19 0091upstream0 ft. AMH - Upstream Manhole, Survey Ends - 11000.4 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish2.8 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO5.6 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO5.6 ft. SRV - Surface Reinforcement Visible, from 10 to 01 o'clock, within 8 inches of joint: NO, Finish8.2 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO11.3 ft. SRV - Surface Reinforcement Visible, from 10 to 01 o'clock, within 8 inches of joint: NO, Start12.5 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO35.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO75 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO101.9 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO107.4 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO160.9 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start168.9 ft. AMH - Downstream Manhole, Survey Begins - 0910168.9 ft. MWL - Water Level, 50 %of cross sectional area168.9 ft. MWM - Water Mark, 60 %of cross sectional area

Observation photos (10)

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

    61.5 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    67 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    93.9 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    133.4 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    156.4 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 01 o'clock, within 8 inches of joint: NO, Start

    157.6 ft. - Surface Reinforcement Visible, from 10 to 01 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO

    160.7 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

    163.3 ft. - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

    166.1 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

Observations (16)

DistanceCodeObservation
8SAV
0AMH0910
67SRV
0MWL
133.4SRV
168.5SAV
0MWM
168.9AMH1100
61.5SRV
166.1SRV
93.9SRV
156.4SRV
163.3SRV
160.7SRC
157.6SRV
163.3SRV

Properties (5)

additional_info
RFIR
custom_field_three
VISIBLE REBAR & AGGREGATE
custom_field_two
2
customer
LACSD
datetime
2017-08-04T08:39:02-07:00