Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 12, 2016, 07:52 AM
  • B 0304_B 0233_20160212_011340.mp4

Date
02/11/2016
W/O
552354
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00086
PipeID
P08814
Time
11:52 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3144
Sewer Name
B JOINT OUTFALL B - UNIT 3A
City
ROSEMEAD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
V
Project
WO_552354_TV15103_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
B 0233
Downstream MH
B 0304
Dir. of Survey
Upstream
Length Surveyed
603.7 ft.
Total Length
603.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2X00
O&M Rating
246
Overall Index
2
Overall Quick
Overall Rating
246
Pipe schematic from manhole B 0233 to B 0304
MH: B 0233MH: B 0304upstream0 ft. MSA - Survey Abandoned - DUE TO DEBRIS SLUDGE IN BOTTOM OF PIPE0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - DEBRIS12 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS303 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"386.2 ft. VR - Vermin - Rat, within 8 inches of joint: YES, 2601.7 ft. MGO - General Observation - MAGNESIUM H.O. START601.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start603.7 ft. MGO - Reversal Inspection603.7 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK603.7 ft. MWL - Water Level, 15 %of cross sectional area603.7 ft. MWM - Water Mark, 20 %of cross sectional area603.7 ft. AMH - Downstream Manhole, Survey Begins - B 0233

Observation photos (5)

  • Reversal Inspection

    0 ft. - Reversal Inspection

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Vermin - Rat, within 8 inches of joint: YES, 2

    217.5 ft. - Vermin - Rat, within 8 inches of joint: YES, 2

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"

    300.7 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"

  • Deposits Settled Other,  10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish - DEBRIS

    603.7 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - DEBRIS

Observations (13)

DistanceCodeObservation
603.7MSADUE TO DEBRIS SLUDGE IN BOTTOM OF PIPE
2MGOMAGNESIUM H.O. START
591.7DSZDEBRIS
2DAGS
603.7DAGS
0MGO
217.5VR
603.7DSZDEBRIS
0MGOLATERAL AT MH 3 OCLOCK
300.7TBA
0MWL
0MWM
0AMHB 0233

Properties (4)

additional_info
SC225531
custom_field_two
5
customer
LACSD
datetime
2016-02-11T23:52:00-08:00