Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2017, 10:56 AM
  • 15 0764_15 0763 _02162017_025647.mp4

Date
02/16/2017
W/O
619124
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00593
PipeID
P12965
Time
2:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4244
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_619124_TV15200_FEB2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0764
Downstream MH
15 0763
Dir. of Survey
Downstream
Length Surveyed
353.3 ft.
Total Length
353.3 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
412M
O&M Rating
144
Overall Index
3
Overall Quick
Overall Rating
354
Pipe schematic from manhole 15 0764 to 15 0763
MH: 15 0764MH: 15 0763downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07642 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start80.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"165.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"169.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"169.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"351.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish351.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish353.3 ft. MGO - General Observation - ACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK353.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE353.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0763

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
126.4TFA
266.6TFA
0MWM
83.7TFA
123.2TF
165.9TFC
199.7TFC
2DAGS
80.5TF
2SAP
351.2SAP
353.3MGOACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
169.3TF
353.3MGOCOCKROACHES IN MANHOLE
0MWL
169.3TF
0AMH15 0764
269.8TFC
351.2DAGS
353.3AMH15 0763

Properties (4)

additional_info
SC306747
custom_field_two
3
customer
LACSD
datetime