Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2017, 05:38 PM
  • J 0268_J 0267_02132017_022309.mpg

Date
01/20/2017
W/O
619078
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00059
PipeID
P11507
Time
9:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4264
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Routine Assessment
Project
WO_619078_TV05169_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0268
Downstream MH
J 0267
Dir. of Survey
Downstream
Length Surveyed
422.1 ft.
Total Length
422.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
252
O&M Index
2
O&M Quick
2P00
O&M Rating
168
Overall Index
3
Overall Quick
Overall Rating
420
Pipe schematic from manhole J 0268 to J 0267
MH: J 0268MH: J 0267downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 02680 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. MGO - General Observation - MAG COATING3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start88.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"422.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish422.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish422.1 ft. AMH - Downstream Manhole, Survey Ends - J 0267422.1 ft. MGO - General Observation - COPPED CONNECTION AT 3 O CLOCK422.1 ft. MGO - General Observation - CONNECTION AT 9 O CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
422.1SAV
422.1DAGS
88.6TBA
422.1AMHJ 0267
422.1MGOCOPPED CONNECTION AT 3 O CLOCK
3.1SAV
0AMHJ 0268
422.1MGOCONNECTION AT 9 O CLOCK
3.1MGOMAG COATING
0MWL
3.1DAGS
0MWM

Properties (4)

additional_info
SC318715
custom_field_two
3
customer
LACSD
datetime
2017-01-20T09:38:09-08:00