Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 06:26 AM
Date
04/05/2016
W/O
563407
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00327
PipeID
P08350
Time
11:26 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3245
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE, CA 90260
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
A 0569
Downstream MH
A 0568
Dir. of Survey
Downstream
Length Surveyed
274.5 ft.
Total Length
274.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole A 0569 to A 0568
MH: A 0569MH: A 0568downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05690 ft. MWL - Water Level, 20 %of cross sectional area3.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"38.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.6 ft. RMB - Roots Medium Barrell, at 10 o'clock, 30 %, within 8 inches of joint: NO75 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"243 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"246 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"272 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish274.5 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK274.5 ft. AMH - Downstream Manhole, Survey Ends - A 0568274.5 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK

Observations (21)

DistanceCodeObservation
51.7TFC
13.2TBA
0MWM
38.9TFA
274.5MGOLATERAL AT MH 3 OCLOCK
272DAGS
194.5TFA
0AMHA 0569
117.1TFA
243TFC
3.2DAGS
0MWL
246TFA
274.5AMHA 0568
75TFA
73.6RMB
158.2TFA
93.7TFC
274.5MGOLATERAL AT MH 9 OCLOCK
125.1TFA
191.7TFA

Properties (4)

additional_info
SC305337
custom_field_two
4
customer
LACSD
datetime
2016-04-05T23:26:49-07:00