Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2016, 11:14 AM
  • B 0293_B 0292_01042016_041527.mp4

Date
04/01/2016
W/O
563385
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00083
PipeID
P08784
Time
4:14 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3303
Sewer Name
B JOINT OUTFALL B - UNIT 1J
City
ROSEMEAD
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_563385_TV15176_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
B 0293
Downstream MH
B 0292
Dir. of Survey
Downstream
Length Surveyed
590.3 ft.
Total Length
590.3 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2V00
O&M Rating
234
Overall Index
2
Overall Quick
Overall Rating
242
Pipe schematic from manhole B 0293 to B 0292
MH: B 0293MH: B 0292downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 02930 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES81.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"192.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"373.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES373.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"422.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"452 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"543 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES553.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"589.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish589.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE590.3 ft. AMH - Downstream Manhole, Survey Ends - B 0292

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    10.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    373.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    543 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    589.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (24)

DistanceCodeObservation
192.2TBA
589.1DAGS
452TF
350.5TF
284.5TB
373.2CL
163.7TB
422.7TBA
10.3CM
553.6TFC
0AMHB 0293
373.9TB
2DAGS
0MWM
590.3AMHB 0292
0MGOCOCKROACHES IN MANHOLE
147.3TFC
81.4TB
589.1MGOCOCKROACHES IN MANHOLE
543CM
151.1TB
232.2TB
0MWL
249.1TF

Properties (4)

additional_info
SC305429
custom_field_two
4
customer
LACSD
datetime