Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2018, 05:40 AM
  • 17 0004_17 0003 _11092018_224031.mp4

Date
09/11/2018
W/O
724194
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00668
PipeID
P13729
Time
10:40 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6001
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
07
Purpose
Routine Assessment
Project
WO_724194_TV17004_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
17 0004
Downstream MH
17 0003
Dir. of Survey
Downstream
Length Surveyed
435.8 ft.
Total Length
435.8 ft.
Structural Index
3
Structural Quick
4P2P
Structural Rating
514
O&M Index
1
O&M Quick
4231
O&M Rating
98
Overall Index
2
Overall Quick
Overall Rating
612
Pipe schematic from manhole 17 0004 to 17 0003
MH: 17 0004MH: 17 0003downstream0 ft. AMH - Upstream Manhole, Survey Begins - 17 00040 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area3 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.5 ft. RML - Roots Medium Lateral, at 02 o'clock, 25 %, within 8 inches of joint: NO13.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"78.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.8 ft. RBL - Roots Ball Lateral, at 10 o'clock, 90 %97.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"202 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"263.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"305 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"405.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"428.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"435.8 ft. AMH - Downstream Manhole, Survey Ends - 17 0003435.8 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish435.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish435.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
13.5RML
435.8AMH17 0003
324.1TF
428.6TF
435.8RFJ
13.5TF
263.4TF
155TF
78.8TF
435.8SSS
3RFJ
97.6TF
148TF
378.8TF
405.4TF
202TF
3SSS
435.8FM
59.2TF
0AMH17 0004
78.8RBL
228.9TF
11.4FM
0MWL
270.4TF
0MWM
305TF

Properties (4)

additional_info
SC364816
custom_field_two
2
customer
LACSD
datetime
2018-09-11T22:40:04-07:00