Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2017, 09:47 AM
  • H 1132_H 1131_05052017_024722.mp4

Date
05/05/2017
W/O
630340
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00166
PipeID
P23952
Time
2:47 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4445
Sewer Name
H JOINT OUTFALL H - UNIT 1G
City
VERNON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
Page No.
03
Purpose
Routine Assessment
Project
WO_630340_TV23003_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 1132
Downstream MH
H 1131
Dir. of Survey
Downstream
Length Surveyed
41.9 ft.
Total Length
41.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole H 1132 to H 1131
MH: H 1132MH: H 1131downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 11320 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start24.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish41.9 ft. AMH - Downstream Manhole, Survey Ends - H 1131

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
24.2TBA
41.9AMHH 1131
0MWL
0AMHH 1132
0MWM
38.1DAGS
2DAGS

Properties (5)

additional_info
SC345218
custom_field_two
4
customer
LACSD
datetime
2017-05-05T02:47:02-07:00
year_laid
36924