Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 18, 2017, 08:44 AM
  • 22 0486_22 0485 _20170418_022843.mp4

Date
04/18/2017
W/O
630167
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00800
PipeID
P16825
Time
1:44 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4355
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
V
Project
WO_630167_TV22031_APR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
22 0486
Downstream MH
22 0485
Dir. of Survey
Downstream
Length Surveyed
336.3 ft.
Total Length
336.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 22 0486 to 22 0485
MH: 22 0486MH: 22 0485downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 04862.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"43.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"91.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"94.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"96.3 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"142.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"145.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"194.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"197.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"242.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"245.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"293.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"296.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"336.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish336.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0485

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
94.7TFC
194.1TF
293.6TF
336.3DAGS
145.8TFC
91.7TFC
142.7TF
2.4DAGS
40.7TF
336.3SAV
0MWL
245.3TFC
0MWM
296.6TFC
43.8TFC
96.3TB
197.1TFC
2.4SAV
242.6TFC
0AMH22 0486
336.3AMH22 0485

Properties (4)

additional_info
SC340719
custom_field_two
3
customer
LACSD
datetime
2017-04-18T01:44:55-07:00