Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2017, 08:33 AM
  • 18 1015_18 1014 _19042017_013328.mp4

Date
04/19/2017
W/O
630156
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00677
PipeID
P14869
Time
1:33 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4268
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_630156_TV18008_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 1015
Downstream MH
18 1014
Dir. of Survey
Downstream
Length Surveyed
294.3 ft.
Total Length
294.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 1015 to 18 1014
MH: 18 1015MH: 18 1014downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 10150 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE2.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - LINER2.1 ft. MGO - General Observation - MAGNESIUM COATING START2.4 ft. VC - Vermin Cockroach73.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"148.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"231.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"232 ft. OBN - Obstacles Construction Debris, 10 %of cross sectional area, from 04 to 08 o'clock, Start - NOT VISIBLE266.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"290.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.1 ft. OBN - Obstacles Construction Debris, 10 %of cross sectional area, from 04 to 08 o'clock, Finish - NOT VISIBLE290.1 ft. MGO - General Observation - MAGNESIUM COATING END294.3 ft. AMH - Downstream Manhole, Survey Ends - 18 1014294.3 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0AMH18 1015
73.4TFA
231.8TFA
2.1DAGS
294.3AMH18 1014
0MWM
266.4TFA
0MWL
148.6TFA
290.1DAGS
232OBNNOT VISIBLE
290.1OBNNOT VISIBLE
2.1MGOLINER
290.1MGOMAGNESIUM COATING END
294.3MGOLATERAL AT MH 3 OCLOCK ACTIVE
2.1MGOMAGNESIUM COATING START
0MGOLATERAL AT MH 3 OCLOCK ACTIVE
2.4VC

Properties (6)

additional_info
SC306848
custom_field_two
4
customer
LACSD
datetime
2017-04-19T01:33:14-07:00
lining
CIPP
year_laid
38344