Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2016, 08:32 AM
  • 18 0409_18 0408_20160321_014156.mp4

Date
03/21/2016
W/O
557858
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00699
PipeID
P14244
Time
1:32 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3229
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_557858_TV18044_2016MAR
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0409
Downstream MH
18 0408
Dir. of Survey
Downstream
Length Surveyed
125.9 ft.
Total Length
125.9 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
72
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
76
Pipe schematic from manhole 18 0409 to 18 0408
MH: 18 0409MH: 18 0408downstream0 ft. MWL - Water Level, 55 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 04092 ft. MGO - General Observation - MAGNEZIUM H.O. START2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"122 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish122.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish125.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0408

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    7 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    122.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (10)

DistanceCodeObservation
122.7DAGS
4.1DAGS
125.9AMH18 0408
2MGOMAGNEZIUM H.O. START
0MWL
7TBA
2SAV
0MWL
0AMH18 0409
122SAV

Properties (4)

additional_info
SC305320
custom_field_two
3
customer
LACSD
datetime