Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2016, 10:49 AM
  • B 0857_B 0856_16032016_035009.mp4

Date
03/16/2016
W/O
557614
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00096
PipeID
P09011
Time
3:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3294
Sewer Name
B JOINT OUTFALL B - UNIT 6B
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_557614_TV15108_2016MAR
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 0857
Downstream MH
B 0856
Dir. of Survey
Downstream
Length Surveyed
583.8 ft.
Total Length
583.8 ft.
Structural Index
3
Structural Quick
3V00
Structural Rating
348
O&M Index
2
O&M Quick
2V00
O&M Rating
232
Overall Index
3
Overall Quick
Overall Rating
580
Pipe schematic from manhole B 0857 to B 0856
MH: B 0857MH: B 0856downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - B 08570 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 70%2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start581.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish581.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish581.8 ft. MGO - General Observation - RUN LIST STATES MH AT 605'.583.8 ft. AMH - Downstream Manhole, Survey Ends - B 0856

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
583.8AMHB 0856
2DAGS
581.8SAP
0MWM
2MGOMAG COATING 70%
0MGOCOCKROACHES IN MANHOLE
0AMHB 0857
581.8DAGS
0MWL
2SAP
581.8MGORUN LIST STATES MH AT 605'.

Properties (5)

additional_info
SC305418
custom_field_three
PROJECTING AGG THROUGHOUT
custom_field_two
3
customer
LACSD
datetime
2016-03-16T03:49:34-07:00