Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2016, 09:42 AM
  • B 0858_B 0857_16032016_024149.mp4

Date
03/16/2016
W/O
557614
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00096
PipeID
P09012
Time
2:42 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3294
Sewer Name
B JOINT OUTFALL B - UNIT 6B
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_557614_TV15108_2016MAR
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 0858
Downstream MH
B 0857
Dir. of Survey
Downstream
Length Surveyed
605.2 ft.
Total Length
605.2 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
360
O&M Index
2
O&M Quick
2W00
O&M Rating
240
Overall Index
3
Overall Quick
Overall Rating
600
Pipe schematic from manhole B 0858 to B 0857
MH: B 0858MH: B 0857downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 08780 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start604.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE604.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish604.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish605.2 ft. AMH - Downstream Manhole, Survey Ends - B 0857

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    604.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
2SAP
0AMHB 0878
604.2MGOCOCKROACHES IN MANHOLE
0MWL
604.2SAP
605.2AMHB 0857
2DAGS
0MWM
0MGOCOCKROACHES IN MANHOLE
604.2DAGS

Properties (5)

additional_info
SC305418
custom_field_three
PROJECTING AGG THROUGHOUT
custom_field_two
3
customer
LACSD
datetime
2016-03-16T02:42:34-07:00