- Date
- 03/15/2016
- W/O
- 557613
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00208
- PipeID
- P00892
- Time
- 1:51 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3291
- Sewer Name
- 01 HOLMES-WILLOWBROOK TRUNK
- City
- LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- WO_557613_TV01033_2016MAR
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Lining Method
- Segmented Panel
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 01 1492
- Downstream MH
- 01 0411A
- Dir. of Survey
- Downstream
- Length Surveyed
- 136.8 ft.
- Total Length
- 136.8 ft.
- Structural Index
- 2
- Structural Quick
- 2200
- Structural Rating
- 4
- O&M Index
- 2
- O&M Quick
- 2D00
- O&M Rating
- 54
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 58
Pipe schematic from manhole 01 1492 to 01 0411A Observation photos (3)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

35 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

103 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES