Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 06:29 AM
  • 05 0927_05 0926_10032016_224238.mp4

Date
03/10/2016
W/O
557872
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00547
PipeID
P06159
Time
10:29 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3283
Sewer Name
05 120TH STREET EXTENSION TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_557872_TV05175_2016MAR
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
05 0927
Downstream MH
05 0926
Dir. of Survey
Downstream
Length Surveyed
339.1 ft.
Total Length
339.1 ft.
Structural Index
3
Structural Quick
3Z00
Structural Rating
399
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
3
Overall Quick
Overall Rating
533
Pipe schematic from manhole 05 0927 to 05 0926
MH: 05 0927MH: 05 0926downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 09270 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 70%2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"120.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"223.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"328.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"337.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish337.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish337.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK339.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE339.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0926

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    339.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
6.7SAP
339.1MGOACTIVE CONNECTION AT MH 3 O'CLOCK
120.4TFC
2DAGS
337.2DAGS
2.7SAV
2MGOMAG COATING 70%
0AMH05 0927
339.1MGOCOCKROACHES IN MANHOLE
337.2SAP
13.7TFC
223.9TFC
339.1AMH05 0926
0MWM
337.2SAV
0MWL
328.3TFC

Properties (4)

additional_info
SC305407
custom_field_two
3
customer
LACSD
datetime
2016-03-10T22:29:06-08:00