Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2016, 08:45 AM
Date
04/04/2016
W/O
563385
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00083
PipeID
P08789
Time
1:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3304
Sewer Name
B JOINT OUTFALL B - UNIT 1J
City
ROSEMEAD
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_563385_TV15176_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 0298
Downstream MH
B 0297
Dir. of Survey
Downstream
Length Surveyed
395.1 ft.
Total Length
395.1 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
2
Overall Quick
Overall Rating
166
Pipe schematic from manhole B 0298 to B 0297
MH: B 0298MH: B 0297downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 02980 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start75.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"92 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES158.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"199.4 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: NO292 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.5 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES347.9 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES393.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish393.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE395.1 ft. AMH - Downstream Manhole, Survey Ends - B 0297

Observations (17)

DistanceCodeObservation
0AMHB 0298
158.7TBA
121.9CS
92TFC
393.1DAGS
199.4CM
0MWL
0MWM
2DAGS
393.1MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
75.5TBA
194.5TFC
292TFC
347.9CM
318.5CS
395.1AMHB 0297

Properties (4)

additional_info
SC305430
custom_field_two
3
customer
LACSD
datetime
2016-04-04T01:45:51-07:00