Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2016, 10:55 AM
  • 02 1302_02 1301B_12082016_030731.mp4

Date
12/08/2016
W/O
607634
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00238
PipeID
P03821
Time
2:55 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3935
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607634_TV02329_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1302
Downstream MH
02 1301B
Dir. of Survey
Downstream
Length Surveyed
141.4 ft.
Total Length
141.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1302 to 02 1301B
MH: 02 1302MH: 02 1301Bdownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13023.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"53.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"88 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"89.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"94.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"125.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"137.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"138.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES140.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"140.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish140.8 ft. OBZ - Obstacles Other, 15 %of cross sectional area, from 03 to 05 o'clock - AT MANHOLE141.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1301B

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    138.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
140.8TFC
0MWL
137.8TF
89.5TFC
140.8DAGS
94.8TF
53.7TF
138.4CM
0MGOLATERAL AT MH 3 O CLOCK
10TF
3.3DAGS
0MWM
125.5TF
88TB
141.4AMH02 1301B
140.8OBZAT MANHOLE
0AMH02 1302

Properties (4)

additional_info
SC317679
custom_field_two
4
customer
LACSD
datetime
2016-12-08T02:55:00-08:00