Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2016, 06:52 AM
  • 02 1325_02 1324_12072016_230917.mp4

Date
12/07/2016
W/O
607634
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00238
PipeID
P03848
Time
10:52 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3935
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_607634_TV02329_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1325
Downstream MH
02 1324
Dir. of Survey
Downstream
Length Surveyed
274.7 ft.
Total Length
274.7 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
18
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole 02 1325 to 02 1324
MH: 02 1325MH: 02 1324downstream0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 02 13250 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area10.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"17 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES27.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES31.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING54.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"77.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"89.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"102.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish140.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES150.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"153.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"184.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"187.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING189.7 ft. FL - Fracture Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Start202.4 ft. FL - Fracture Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Finish204.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"209.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"212.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"214.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start243.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish265.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish274.7 ft. VC - Vermin Cockroach274.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1324

Observation photos (8)

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    17 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    27.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING

    31.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

    102.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    140.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING

    187.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - WANDERING

  • Fracture Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Start

    189.7 ft. - Fracture Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    214.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
140.1CL
274.7VC
265.2CL
204.3TFA
214.3FM
0VC
10.8TFC
27.9CL
212.4TFC
184.4TFC
150.9TFC
0AMH02 1325
54.5TFC
189.7FL
153.5TFC
187.3CLWANDERING
17CM
77.3TFC
202.4FL
31.7CLWANDERING
0MWL
243.9FM
0MWM
274.7AMH02 1324
209.7TFA
102.4CL
89.9TFC

Properties (4)

additional_info
SC317679
custom_field_two
2
customer
LACSD
datetime
2016-12-07T22:52:00-08:00