Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2016, 11:06 AM
  • 29 0684_29 0683 _11182016_030710.mp4

Date
11/18/2016
W/O
596943
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01116
PipeID
P24716
Time
3:06 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4018
Sewer Name
29 SPRING STREET SEWER
City
SIGNAL HILL
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_596943_TV29029_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0684
Downstream MH
29 0683
Dir. of Survey
Downstream
Length Surveyed
305.8 ft.
Total Length
305.8 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 29 0684 to 29 0683
MH: 29 0684MH: 29 0683downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 06840 ft. MWL - Water Level, 5 %of cross sectional area8.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"25.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"39 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"61.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"96.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"128.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"178.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"190.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"226.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"278.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"294.6 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"294.6 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Start302.5 ft. MWLS - Water Level, Sag in pipe, 20 %of cross sectional area, Finish305.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0683

Observation photos (1)

  • Water Level, Sag in pipe, 20 %of cross sectional area, Start

    294.6 ft. - Water Level, Sag in pipe, 20 %of cross sectional area, Start

Observations (20)

DistanceCodeObservation
294.6TFA
61.5TF
302.5MWLS
8.9TFA
144.9TB
39TBA
226.4TFC
0MWM
0AMH29 0684
278.8TFC
96.4TFC
305.8AMH29 0683
178.1TFC
128.8TFC
294.6MWLS
77.2TFC
119.4TFC
0MWL
25.1TFC
190.4TFC

Properties (4)

additional_info
SC306410
custom_field_two
4
customer
LACSD
datetime
2016-11-18T03:06:28-08:00