Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 26, 2016, 11:07 AM
  • 14 0154_14 0153A_10262016_040831.mp4

Date
10/26/2016
W/O
592016
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P25790
Time
4:07 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3794
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_592016_TV14035_SEP2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0153A
Downstream MH
14 0154
Dir. of Survey
Upstream
Length Surveyed
152 ft.
Total Length
152 ft.
Structural Index
2
Structural Quick
322B
Structural Rating
32
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 14 0153A to 14 0154
MH: 14 0153AMH: 14 0154upstream0 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 14 0154, ABANDONED MH.0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish18.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"21.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start66.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start152 ft. AMH - Downstream Manhole, Survey Begins - 14 0153A152 ft. MWL - Water Level, 5 %of cross sectional area - NO FLOW

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    87.3 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Upstream Manhole, Survey Ends - 14 0154, ABANDONED MH.

    152 ft. - Upstream Manhole, Survey Ends - 14 0154, ABANDONED MH.

Observations (13)

DistanceCodeObservation
152SSS
2SAP
0AMH14 0153A
133.6TFC
87.3SSS
152AMH14 0154, ABANDONED MH.
0MWLNO FLOW
35TFC
82.7TFC
85.3TFC
130.7TFC
152SAP
32.4TFC

Properties (4)

additional_info
SC306332
custom_field_two
2
customer
LACSD
datetime
2016-10-26T04:07:51-07:00