Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2018, 05:47 AM
  • 16 0049_16 0048 _09062018_224734.mp4

Date
09/06/2018
W/O
723896
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00639
PipeID
P13062
Time
10:47 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6024
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Routine Assessment
Project
WO_723896_TV16113_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0049
Downstream MH
16 0048
Dir. of Survey
Downstream
Length Surveyed
359.5 ft.
Total Length
359.5 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
204
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole 16 0049 to 16 0048
MH: 16 0049MH: 16 0048downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 00490 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area15.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start357.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE357.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish359.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0048

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    357.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (7)

DistanceCodeObservation
357.8MGOCOCKROACHES IN MANHOLE
359.5AMH16 0048
0AMH16 0049
357.8CM
15.6CM
0MWL
0MWM

Properties (4)

additional_info
SC364788
custom_field_two
3
customer
LACSD
datetime
2018-09-06T22:47:11-07:00