Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2018, 08:01 AM
  • 08 0330_08 0329_09182018_010203.mp4

Date
09/18/2018
W/O
723814
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00013
PipeID
P00379
Time
1:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6029
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_723814_TV08155_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0329
Downstream MH
08 0330
Dir. of Survey
Upstream
Length Surveyed
333.9 ft.
Total Length
333.9 ft.
Structural Index
3
Structural Quick
3B24
Structural Rating
53
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
185
Pipe schematic from manhole 08 0329 to 08 0330
MH: 08 0329MH: 08 0330upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 08 03300 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish73.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES86 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish198.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start199.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.5 ft. CS - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES235.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"285.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"331.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start333.9 ft. MWL - Water Level, 10 %of cross sectional area333.9 ft. AMH - Downstream Manhole, Survey Begins - 08 0329333.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE333.9 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    102.4 ft. - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    135.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    255.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    260.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    333.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
2DAGS
0MWL
332DAGS
135.7CL
200.6TFC
260.4CM
134.8TFA
0AMH08 0329
255.3CM
48.2TFC
333.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
150.1CL
98.5TFC
102.4CS
333.9AMH08 0330
332CM
152TFC
333.9MGOCOCKROACHES IN MANHOLE
247.9TFC
0MWM

Properties (4)

additional_info
SC364793
custom_field_two
2
customer
LACSD
datetime
2018-09-18T01:01:45-07:00