- Date
- 09/26/2018
- W/O
- 718146
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00031
- PipeID
- P11329
- Time
- 2:55 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6046
- Sewer Name
- E JOINT OUTFALL E - UNIT 4 RELOCATION
- City
- LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- WO_718146_TV01089_AUG2018
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- E 0102
- Downstream MH
- E 0101
- Dir. of Survey
- Downstream
- Length Surveyed
- 39.4 ft.
- Total Length
- 39.4 ft.
- Structural Index
- 3
- Structural Quick
- 5237
- Structural Rating
- 45
- O&M Index
- 2
- O&M Quick
- 4127
- O&M Rating
- 18
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 63
Pipe schematic from manhole E 0102 to E 0101 Observation photos (5)

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

29.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

39.4 ft. - General Observation - COCKROACHES IN MANHOLE