Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2018, 06:46 AM
  • 15 0400_15 0399 _09262018_000543.mp4

Date
09/25/2018
W/O
729406
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00597
PipeID
P12323
Time
11:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6044
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_729406_TV15214_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0400
Downstream MH
15 0399
Dir. of Survey
Downstream
Length Surveyed
253.9 ft.
Total Length
253.9 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
156
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
3
Overall Quick
Overall Rating
256
Pipe schematic from manhole 15 0400 to 15 0399
MH: 15 0400MH: 15 0399downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 04000 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.1 ft. B - Broken, from 07 to 11 o'clock, within 8 inches of joint: YES158.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"162.5 ft. RPZ - Repair Other, within 8 inches of joint: YES, Start - LINK PIPE165.8 ft. RPZ - Repair Other, within 8 inches of joint: YES, Finish167.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. B - Broken, from 09 to 10 o'clock, within 8 inches of joint: YES252 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE253.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0399253.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 07 to 11 o'clock, within 8 inches of joint: YES

    154.1 ft. - Broken, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Repair Other, within 8 inches of joint: YES, Start - LINK PIPE

    162.5 ft. - Repair Other, within 8 inches of joint: YES, Start - LINK PIPE

  • Broken, from 09 to 10 o'clock, within 8 inches of joint: YES

    247.1 ft. - Broken, from 09 to 10 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    253.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (25)

DistanceCodeObservation
253.9MGOCOCKROACHES IN MANHOLE
165.8RPZ
0MWL
7.6TFC
162.5RPZLINK PIPE
57.5TFC
167.2TFC
5CM
213.1TFC
252CM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
158.4TFC
47.3TFC
112.2TFC
252DAGS
245.2TFC
204.4TFC
253.9AMH15 0399
0AMH15 0400
247.1B
2DAGS
106TFC
0MWM
154.1B
253.9MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Properties (4)

additional_info
SC365107
custom_field_two
2
customer
LACSD
datetime
2018-09-25T23:46:02-07:00