Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2018, 09:04 AM
  • 05 1726_05 1725_10172018_021842.mp4

Date
10/17/2018
W/O
0734495
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06953
Time
2:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1016
Sewer Name
05 LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20181012MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1726
Downstream MH
05 1725
Dir. of Survey
Downstream
Length Surveyed
321.8 ft.
Total Length
321.8 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
53
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
57
Pipe schematic from manhole 05 1726 to 05 1725
MH: 05 1726MH: 05 1725downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM9.3 ft. MGP - General Photograph - 21" VCP15.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE24.1 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - SLIGHT24.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H36.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H39.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H39.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H43.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: NO - H55.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open107.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open109.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H115.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL115.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H115.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL115.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H164.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL174.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - SL192.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H196.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SL196.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open207 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL207 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H216.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL224 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL228.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL232.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H250.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H275.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H290.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open299.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H312.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - SL312.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SL321.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active321.8 ft. AMH - Downstream Manhole, Survey Ends - 3:15AM

Observation photos (7)

  • General Photograph - 21" VCP

    9.3 ft. - General Photograph - 21" VCP

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

    39.3 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

    39.3 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

    115.9 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

    115.9 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

    216.9 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

    224 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

Observations (38)

DistanceCodeObservation
36.3FLH
228.8FCSL
164.7FCSL
321.1MGOConn. @ Mh, 9 O' Clock. Active
290.3TFOpen
196.2FLSL
192.5FCH
216.9FLSL
174.5FLSL
312.1FLSL
0MGOConn. @ Mh, 9 O' Clock. Capped
224FLSL
24.1FCSLIGHT
15.5FLHAIRLINE
107.9TFOpen
24.1FCH
115.9FLSL
196.2TFOpen
115.9FLH
0MWL
321.8AMH3:15AM
250.1FLH
232.3FCH
0MWM
115.9FLSL
299.3FCH
115.9FLH
9.3MGP21" VCP
312.1FLSL
39.3FLH
109.7FCH
55.7TFOpen
275.3FCH
207FLSL
39.3FLH
207FLH
0AMH2:20AM
43.9FCH

Properties (4)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2018-10-17T02:04:35-07:00