Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2015, 07:31 AM
  • 02 1289_02 1288_20151214233315.mp4

Date
12/14/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03806
Time
11:31 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2850
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 1289
Downstream MH
02 1288
Dir. of Survey
Downstream
Length Surveyed
307 ft.
Total Length
307 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
307
Pipe schematic from manhole 02 1289 to 02 1288
MH: 02 1289MH: 02 1288downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12890 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start166.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES307 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish307 ft. AMH - Downstream Manhole, Survey Ends - 02 1288307 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK307 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
3.9CM
166.6TBA
307DAGS
307AMH02 1288
307MGOACTIVE CONNECTION AT MH 9 O'CLOCK
166.8DAGS
2DAGS
307CM
0AMH02 1289
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL

Properties (4)

additional_info
SC204184
custom_field_two
3
customer
LACSD
datetime
2015-12-14T23:31:36-08:00