Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2018, 09:06 AM
  • 08 0082_08 0081 _11042018_021736.mp4

Date
04/11/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00110
Time
2:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5527
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
08 0082
Downstream MH
08 0081
Dir. of Survey
Downstream
Length Surveyed
165.7 ft.
Total Length
165.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 08 0082 to 08 0081
MH: 08 0082MH: 08 0081downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00820 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH11.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"30.5 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.7 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH165.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish165.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0081

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    30.5 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
30.5TS
0MWL
114.6TF
0AMH08 0082
165.7MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0MWM
11.2CM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
165.7CM
63.1TFC
165.7AMH08 0081
15.7TFC

Properties (4)

additional_info
SC358734
custom_field_two
3
customer
LACSD
datetime
2018-04-11T02:06:22-07:00