Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2018, 05:37 AM
  • 08 0072_08 0071 _11042018_224942.mp4

Date
04/11/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00074
Time
10:37 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5528
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0071
Downstream MH
08 0072
Dir. of Survey
Upstream
Length Surveyed
333.9 ft.
Total Length
333.9 ft.
Structural Index
3
Structural Quick
3H22
Structural Rating
145
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
145
Pipe schematic from manhole 08 0071 to 08 0072
MH: 08 0071MH: 08 0072upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00723.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish47.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.7 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start248 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES264.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES300.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.9 ft. MWM - Water Mark, 20 %of cross sectional area333.9 ft. AMH - Downstream Manhole, Survey Begins - 08 0071333.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK333.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    69.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    72.1 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    93.6 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    204.2 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
33.8TF
0MWM
204.2TS
72.1CL
85.9TFC
69.2CL
134.6TFC
234.3TFC
93.6CM
186.1TFC
286.1TF
0AMH08 0071
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
333.9AMH08 0072
330.3CM

Properties (4)

additional_info
SC358735
custom_field_two
3
customer
LACSD
datetime
2018-04-11T22:37:08-07:00