Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2018, 06:20 AM
  • 08 0066_08 0065 _11042018_233239.mp4

Date
04/11/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00068
Time
11:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5528
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0065
Downstream MH
08 0066
Dir. of Survey
Upstream
Length Surveyed
333 ft.
Total Length
333.1 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
260
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
263
Pipe schematic from manhole 08 0065 to 08 0066
MH: 08 0065MH: 08 0066upstream0 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 08 006648.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. RML - Roots Medium Lateral, at 02 o'clock, 35 %, within 8 inches of joint: NO199.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start333.1 ft. MWL - Water Level, 5 %of cross sectional area333.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK333.1 ft. AMH - Downstream Manhole, Survey Begins - 08 0065333.1 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
333.1FM
0MWL
232.7TFC
80.9TF
133.6RML
284.2TF
28.8TFC
0MGOCONNECTION AT MH 9 O'CLOCK
180.8TFC
133.6TF
0AMH08 0065
333.1AMH08 0066
0MWM
5.7FM

Properties (4)

additional_info
SC358735
custom_field_two
2
customer
LACSD
datetime