Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2018, 08:35 AM
  • 08 0084_08 0083 _11042018_015515.mp4

Date
04/11/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00112
Time
1:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5527
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
08 0084
Downstream MH
08 0083
Dir. of Survey
Downstream
Length Surveyed
397.3 ft.
Total Length
397.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 08 0084 to 08 0083
MH: 08 0084MH: 08 0083downstream0 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT0 ft. AMH - Upstream Manhole, Survey Begins - 08 00840 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 30 %of cross sectional area0.4 ft. MWM - Water Mark, 45 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.7 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YESR55.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"58.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start108.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"257.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"358.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"394.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish394.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish397.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0083

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    58.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

Observations (18)

DistanceCodeObservation
257.9TFC
207.4TFC
3.1CM
397.3AMH08 0083
55.5TFC
394.2RFJ
0.4MWM
308.6TFC
0MGOCAPPED CONNECTION AT 9 O' CLOCK AT
0AMH08 0084
108.6TFC
38.7RFJ
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
58.7RFJ
394.2CM
159.5TFC
358.2TFC
0MWL

Properties (4)

additional_info
SC358734
custom_field_two
3
customer
LACSD
datetime
2018-04-11T01:35:16-07:00