Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2016, 10:32 AM
  • 15 0983_15 0982_29032016_033257.mp4

Date
03/29/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P12758
Time
3:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3299
Sewer Name
15 VALINDA TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
15 0983
Downstream MH
15 0982
Dir. of Survey
Downstream
Length Surveyed
328.5 ft.
Total Length
328.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 15 0983 to 15 0982
MH: 15 0983MH: 15 0982downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 09832 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start42 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.3 ft. CS - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES94 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"201.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"317.8 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: NO326.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE328.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0982

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

    80.3 ft. - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: NO

    317.8 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MANHOLE

    328.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
0MWL
42TFC
328.5MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
256.2TFA
0MWM
328.5AMH15 0982
0AMH15 0983
326.3DAGS
317.8CM
80.3CS
201.2TFC
316.8TFC
2DAGS
145.4TFA
94TFA

Properties (4)

additional_info
SC305425
custom_field_two
4
customer
LACSD
datetime
2016-03-29T03:32:36-07:00