Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2015, 08:22 AM
  • 02 1284_02 1283_20151215002244.mp4

Date
12/15/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03801
Time
12:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2850
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 1284
Downstream MH
02 1283
Dir. of Survey
Downstream
Length Surveyed
303 ft.
Total Length
303 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
161
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
2
Overall Quick
Overall Rating
361
Pipe schematic from manhole 02 1284 to 02 1283
MH: 02 1284MH: 02 1283downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 12840 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start25.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES37.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start105.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start286.8 ft. RPZ - Repair Other, within 8 inches of joint: YES - LINK PIPE303 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK303 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish303 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish303 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish303 ft. AMH - Downstream Manhole, Survey Ends - 02 1283

Observation photos (3)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    25.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    37.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES  - LINK PIPE

    286.8 ft. - Repair Other, within 8 inches of joint: YES - LINK PIPE

Observations (14)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
303MGOACTIVE CONNECTION AT MH 9 O'CLOCK
37.6CM
303CM
303DAGS
303DAE
0AMH02 1284
303AMH02 1283
2DAGS
0MWM
0MWL
286.8RPZLINK PIPE
105.2DAE
25.2CL

Properties (4)

additional_info
SC204184
custom_field_two
3
customer
LACSD
datetime
2015-12-15T00:22:25-08:00