- Date
- 05/04/2016
- W/O
- 563376
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00279
- PipeID
- P04585
- Time
- 12:29 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3337
- Sewer Name
- 02 MONTEBELLO TRUNK
- City
- BELL GARDENS
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- RFIR_WO_563376_TV02334_APRIL2016
- Sewer Type
- GRAVITY
- Material
- NRCP
- Shape
- Circular
- Height
- 21 in.
- Upstream MH
- 02 0947A
- Downstream MH
- H 0188
- Dir. of Survey
- Downstream
- Length Surveyed
- 122.8 ft.
- Total Length
- 122.8 ft.
- Structural Index
- 3
- Structural Quick
- 3D2D
- Structural Rating
- 120
- O&M Index
- 2
- O&M Quick
- 2D00
- O&M Rating
- 48
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 168
Pipe schematic from manhole 02 0947A to H 0188 Observation photos (4)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start