Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2018, 07:52 AM
  • H 1339_H 1338_1052018_043926.mp4

Date
10/05/2018
W/O
0731552
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01184
PipeID
P25882
Time
12:52 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0997
Sewer Name
H JOINT OUTFALL H - UNIT 8L RELIEF
City
AZUSA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Maintenance Related
Project
20181005MDM_JOINT_OUTFALL_H_UNIT_8L_RELIEF
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
H 1339
Downstream MH
H 1338
Dir. of Survey
Downstream
Length Surveyed
120.6 ft.
Total Length
120.6 ft.
Structural Index
2
Structural Quick
2800
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole H 1339 to H 1338
MH: H 1339MH: H 1338downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area10 ft. MGO - General Observation - 24" VCP11.4 ft. MGP - General Photograph - 10:0017.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE17.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLE JOINT FILLER19.5 ft. SSS - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING VCP24.3 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - PEELING VCP24.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP45.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP47.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING VCP65.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING VCP83.8 ft. MGP - General Photograph - 24" VCP VCP120 ft. SSS - Surface Spalling, from 08 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING OUTER SURFACE120.6 ft. MSA - Survey Abandoned - 4:55AM

Observation photos (12)

  • General Observation - 24" VCP

    10 ft. - General Observation - 24" VCP

  • General Photograph - 10:00

    11.4 ft. - General Photograph - 10:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE

    17.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLE JOINT FILLER

    17.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLE JOINT FILLER

  • Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING VCP

    19.5 ft. - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING VCP

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - PEELING VCP

    24.3 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - PEELING VCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP

    24.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP

    45.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING VCP

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING VCP

    47.5 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING VCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING VCP

    65.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING VCP

  • General Photograph - 24" VCP VCP

    83.8 ft. - General Photograph - 24" VCP VCP

  • Survey Abandoned - 4:55AM

    120.6 ft. - Survey Abandoned - 4:55AM

Observations (16)

DistanceCodeObservation
120SSSPEELING OUTER SURFACE
47.5SSSPEELING VCP
10MGO24" VCP
0AMH4:35AM
45.6SSSPEELING VCP
24.3SSSPEELING VCP
11.4MGP10:00
0MWM
17.1SSSPEELING OUTER SURFACE
17.1SSSPOSSIBLE JOINT FILLER
120.6MSA4:55AM
24.3SSSPEELING VCP
19.5SSSPEELING VCP
83.8MGP24" VCP VCP
65.7SSSPEELING VCP
0MWL

Properties (4)

additional_info
PRE CLEANING
customer
LACSD
datetime
2018-10-05T00:52:51-07:00
year_laid
20080424